Conduit and Tubing Fill: Chapter 9 Tables 1, 4, 5 and 8 and the Nipple Rule
Conduit fill is the calculation the Wiring Methods area is built around: two calculation items on the Journeyman and Master exams and a regular Residential Wireman question. The exam is open book, so the skill is knowing *which table, which column, and which rounding rule* — fast. Written from the 2026 text of Chapter 9.
NFPA 70 National Electrical Code, 2026 edition · Reviewed 2026-09-19
Conduit fill is the calculation the Wiring Methods area is built around: two calculation items on the Journeyman and Master exams and a regular Residential Wireman question. The exam is open book, so the skill is knowing which table, which column, and which rounding rule — fast. Written from the 2026 text of Chapter 9.
1. The rule — Table 1
Table 1 — maximum percent of the raceway's cross-sectional area that conductors and cables may occupy:
| Number of conductors and/or cables | Fill |
|---|---|
| 1 | 53% |
| 2 | 31% |
| Over 2 | 40% |
Why 31% for two? Two round conductors side by side waste the space between them — the code is deliberately conservative there.
Notes to Table 1 that get tested:
- Annex C tables give the maximum number of same-size conductors per trade size — use them when every conductor is the same type and size.
- Table 1 applies to complete conduit or tubing systems, not to short sleeves used only to protect exposed wiring or cable from damage.
- Equipment grounding and bonding conductors count in the fill, using their actual dimensions (insulated or bare).
- Nipples: a conduit or tubing nipple not over 24 in. long between boxes, cabinets or similar enclosures may be filled to 60 percent, and the 310.15(C)(1) adjustment factors do not apply.
- Conductors not in Chapter 9 (multiconductor cables, optical fiber cables) — use actual dimensions.
- Mixed sizes — use actual dimensions or Table 5 / 5A for the conductors and Table 4 for the raceway.
- Rounding, same-size conductors: if the calculated count has a decimal of 0.8 or more, round UP to the next whole number. Below 0.8, round down. (Sizing a raceway for a single conductor or cable: a result of 0.8 or more permits one.)
- Bare conductors — Table 8 dimensions.
- A multiconductor cable, optical fiber cable or flexible cord of two or more conductors is treated as a single conductor; an elliptical cable uses its major diameter as the diameter of a circle. Assemblies of single insulated conductors without an overall covering are counted as individual