Cabinets and Wire-Bending Space (312), Underground Wiring (Table 300.7(A)), and the Article 300 General Rules
Two named sub-topics — "Cabinets and Panels" and "Underground Wiring" — plus the general rules of Article 300 that every other wiring-method question assumes. Article 300 was renumbered in 2026: 300.3 → 300.5 (conductors), 300.4 → 300.6 (protection), 300.5 → 300.7 (underground), 300.15 → 300.17 (boxes), 300.17 → 300.19 (fill), 300.19 → 300.21 (vertical supports). Article 312 was also renumbered: 312.5 → 312.8 (enclosures/cable entries), 312.6 → 312.9 (wire-bending space), 312.8 → 312.11 (splices in switch enclosures). Written from the 2026 text.
NFPA 70 National Electrical Code, 2026 edition · Reviewed 2026-09-19
Two named sub-topics — "Cabinets and Panels" and "Underground Wiring" — plus the general rules of Article 300 that every other wiring-method question assumes. Article 300 was renumbered in 2026: 300.3 → 300.5 (conductors), 300.4 → 300.6 (protection), 300.5 → 300.7 (underground), 300.15 → 300.17 (boxes), 300.17 → 300.19 (fill), 300.19 → 300.21 (vertical supports). Article 312 was also renumbered: 312.5 → 312.8 (enclosures/cable entries), 312.6 → 312.9 (wire-bending space), 312.8 → 312.11 (splices in switch enclosures). Written from the 2026 text.
1. Underground wiring — 300.7 and Table 300.7(A)
Table 300.7(A) minimum cover, in inches (measured from the top of the conductor/raceway to the finished surface):
| Location | Col. 1 Direct burial cables/conductors | Col. 2 RMC / IMC | Col. 3 Nonmetallic raceways listed for direct burial (PVC, RTRC) | Col. 4 Residential 120 V, ≤ 20 A, GFCI-protected branch circuits | Col. 5 ≤ 30 V irrigation / landscape lighting (UF, listed cable) |
|---|---|---|---|---|---|
| All locations not specified below | 24 | 6 | 18 | 12 | 6 |
| In trench below ≥ 2-in. concrete | 18 | 6 | 12 | 6 | 6 |
| Under a building | 0 (in raceway, or MC/MI listed for direct burial) | 0 | 0 | 0 | 0 |
| Under ≥ 4-in. exterior concrete slab, no vehicles, slab extending ≥ 6 in. beyond | 18 | 4 | 4 | 6 direct / 4 in raceway | 6 direct / 4 in raceway |
| Under streets, highways, roads, alleys, driveways and parking lots | 24 | 24 | 24 | 24 | 24 |
| One- and two-family dwelling driveways and outdoor parking (dwelling use only) | 18 | 18 | 18 | 12 | 18 |
| Airport runways / adjacent taxiways | 18 | 18 | 18 | 18 | 18 |
Notes that get tested: raceways approved for burial only where concrete-encased need a ; lesser depths are permitted where conductors rise for terminations or splices; Column 4/5 circuits may use the shallowest depth of any method in Columns 1–3; in solid rock, a metal raceway or a nonmetallic raceway listed for direct burial may be covered by extending to the rock; pool/spa/fountain lighting ≤ 30 V in