Miscellaneous Equipment and Limited-Energy Systems: Signs (600), Elevators (620), Welders (630), Class 1/2/3/4 Circuits (720–726), Fire Alarm (760) and Communications (750/800)
Two PSI sub-bullets under *Special Occupancies, Equipment & Conditions* were still uncovered: Miscellaneous Equipment (signs, elevators, welders) and Data Processing and Communications Equipment (the limited-energy and fire alarm circuits of Chapter 7 and the communications articles of Chapter 8). The 2026 edition rebuilt Chapter 7: the old 725 was split into a general article (720), power sources (721), cables (722), raceways (723), Class 1 (724), Class 2/3 (725) and the new Class 4 fault-managed power (726); grounding moved to 750; fire-resistive cable systems are the new Article 772. Everyt
NFPA 70 National Electrical Code, 2026 edition · Reviewed 2026-09-19
Two PSI sub-bullets under Special Occupancies, Equipment & Conditions were still uncovered: Miscellaneous Equipment (signs, elevators, welders) and Data Processing and Communications Equipment (the limited-energy and fire alarm circuits of Chapter 7 and the communications articles of Chapter 8). The 2026 edition rebuilt Chapter 7: the old 725 was split into a general article (720), power sources (721), cables (722), raceways (723), Class 1 (724), Class 2/3 (725) and the new Class 4 fault-managed power (726); grounding moved to 750; fire-resistive cable systems are the new Article 772. Everything below was read from the 2026 text.
1. Electric signs and outline lighting — Article 600
- Listing (600.2): fixed, mobile or portable signs, section signs, outline lighting, PV-powered signs and retrofit kits are listed and labeled regardless of voltage (field-installed skeleton tubing and outline lighting made of listed luminaires excepted).
- The sign outlet (600.5(A)): each commercial building and each commercial occupancy accessible to pedestrians gets at least one sign outlet at each entrance to each tenant space, on a branch circuit rated at least 20 A that supplies no other load (sign controllers excepted; not required at delivery/service entrances).
- Ratings (600.5(C)): sign branch circuits are continuous loads; neon → not over 30 A; all other signs and outline lighting → not over 20 A.
- Wiring (600.5(D)): the supply terminates in the sign, an enclosure, a box, a conduit body or a panelboard; listed sign enclosures may be pull/junction boxes up to 600 V for adjacent signs, outline lighting and the sign's floodlights; poles may enclose the supply conductors.
- Disconnect (600.6): every sign/outline lighting system/skeleton tubing (and its feeder or branch circuit) is controlled by an externally operable switch or breaker that opens all ungrounded conductors and controls no other load. Exceptions: exit directional signs inside a building and cord-and-plug signs. Location — at the point of entry to the sign enclosure/body/pole, opening a