Generators (Article 445) and Transformers (Article 450): Conductors, Overcurrent Protection, Disconnects and Locations
"Generators" is the second sub-topic of Motors & Generators. Transformer overcurrent protection (Table 450.5(B)) is the other classic Master calculation in this neighborhood, so it lives here too. Written from the 2026 text.
NFPA 70 National Electrical Code, 2026 edition · Reviewed 2026-09-19
"Generators" is the second sub-topic of Motors & Generators. Transformer overcurrent protection (Table 450.5(B)) is the other classic Master calculation in this neighborhood, so it lives here too. Written from the 2026 text.
1. Generators — Article 445
- 445.2: stationary generators shall be listed (one-of-a-kind/custom units may be field labeled). 445.10: located per 430.14 (ventilation, maintenance).
- 445.11 nameplate: manufacturer, rated frequency, phases, rating in kW or kVA, power factor, normal volts and amperes, rated ambient temperature; whether or not the neutral is bonded to the frame (field changes get additional marking); generators over 15 kW also provide reactances, power rating category (prime/standby/continuous), temperature rise and insulation class, overload protection method, and available fault current (inverter types).
- 445.12 overcurrent: constant-voltage generators protected from overload by inherent design, breakers, fuses, protective relays or other identified means; two-wire dc generators — one OCPD actuated by the entire generated current (not in the shunt field); generators ≤ 65 V driven by individual motors — the motor OCPD suffices if it operates at ≤ 150 % of the generator's full-load current. Vital generators may alarm instead of trip.
- 445.13(A) conductors, no overcurrent protection at the generator: ampacity from the generator terminals to the first distribution device containing overcurrent protection ≥ 115 % of the nameplate current (100 % where the design prevents overloading). (B): with a listed OCPD or CT/overcurrent relay at the generator, conductors may be tapped from the load side per 240.21(B) (not for portable generators ≤ 15 kW with inaccessible field terminals). (C): neutral sized per 120.61; (D): grounding/bonding conductors carrying fault current per 250 Parts V and VI.
- 445.14: live parts over 50 V ac / 60 V dc guarded. 445.17: terminal housings per 430.12, sized from the hp in Tables 430.247–430.250 that matches the generator's full-load current.
- **445.18(A) disconnecting means: every gene